HV580L Series Frequency Inverter
153
PA-02
PID Feedback source
Default
0
Setting range
0
VS
1
AS
2
VS2
3
VS
-
AS
4
PULSE Pulse ( X5 )
5
Communication
6
VS+AS
7
MAX(|VS|,|AS|)
8
MIN (|VS|,|AS|)
This parameter is used to select the feedback signal channel of process PID.
The PID feedback is a relative value and ranges from 0.0% to 100.0%.
PA-03
PID action direction
Default
0
Setting range
0
Forward action
1
Reverse action
0: Forward action
When the feedback value is smaller than the PID setting, the AC drive's output frequency rises. For example,
the winding tension control requires forward PID action.
•
1: Reverse action
When the feedback value is smaller than the PID setting, the AC drive's output frequency reduces. For
example, the unwinding tension control requires reverse PID action.
Note that this function is influenced by the DI function 35 "Reverse PID action direction".
PA-04
PID setting
feedback range
Default
1000
Setting range
0
~
65535
This parameter is a non-dimensional unit. It is used for PID setting display (C-15) and PID feedback display (C-16).
Relative value 100% of PID setting feedback corresponds to the value of FA-04. If FA-04 is set to 2000 and
PID setting is 100.0%, the PID setting display (C-15) is 2000.PID
PA-05
Proportional gain Kp1
Default
20.0
Setting range
0.0
~
100.0
PA-06
Integral time Ti1
Default
2.00s
Setting range
0.01s
~
10.00s
PA-07
Differential timeTd1
Default
0.000s