HV580L Series Frequency Inverter
50
Function
Code
Parameter Name
Setting Range
Default
Property
P6-08
Time proportion of S-curve
start segment
0.0%
~
(100.0%-P6-09)
80.0%
★
P6-09
Time proportion of S-curve
end segment
0.0%
~
(100.0%-P6-08)
10.0%
★
P6-10
Stop mode
0: Decelerate to stop
1: Coast to stop
0
☆
P6-11
Initial frequency of stop DC
braking
0.00 Hz to maximum frequency 0.00Hz
☆
P6-12
Waiting time of stop DC
braking
0.0s
~
100.0s
0.0s
☆
P6-13
Stop DC braking current
0%
~
100%
30%
☆
P6-14
Stop DC braking time
0.0s
~
5.0s
0.5s
☆
P6-15
Stop DC braking time
0%
~
100%
100%
☆
P6-26
Time proportion of S-curve at
Decel start
0.0% to Min[(100.0% - F6-27),
80%]
20%
☆
P6-27
Time proportion of S-curve at
Decel start
0.0% to Min[(100.0% - F6-26),
80%]
30%
☆
Group P7: Operation Panel and Display
P7-01
MF Key function selection
0: MF.K key disabled
1
:
Switchover between
operation panel control and
remote command control
(terminal or communication)
2
:
Positive & negative switching
3: Forward JOG
4: Reverse JOG
0
★
P7-02
STOP/RESET key function
0: STOP/RESET key enabled
only in operation panel control
1: STOP/RESET key enabled in
any operation mode
1
☆