HV580L Series Frequency Inverter
111
Figure 6-9 Setting of three-line mode 2
As shown in the preceding figure, if SB1 is ON, the AC drive starts running when SB2 is pressed to be ON; the
AC drive instructs forward rotation when K is OFF and instructs reverse rotation when K is ON. The AC drive
stops immediately after SB1 becomes OFF. During normal startup and running, SB1 must remain ON. The AC
drive's running state is determined by the final actions of SB1, SB2 and K.
P4-12
Terminal UP/DOWN rate Default
1.00Hz/s
Setting Range
0.01Hz/s
~
65.535Hz/s
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of terminal
UP/DOWN.
If P0-22 (Frequency reference resolution) is 2, the setting range is 0.001
–65.535 Hz/s.
If P0-22 (Frequency reference resolution) is 1, the setting range is 0.01
–655.35 Hz/s.
P4-13
VS curve 1 minimum input
Default
0.00V
Setting Range
0.00V
~
P4-15
P4-14
Corresponding setting of VS
curve 1 minimum input
curve 1 minimum input
Default
0.0%
Setting Range
-100.00%
~
100.0%