HV580L Series Frequency Inverter
157
Figure 6-27 PID initial value function
PA-23
Maximum deviation between
two PID outputs in forward
direction
Default
1.00%
Setting range
0.00%
~
100.00%
PA-24
Maximum deviation between
two PID outputs in reverse
direction
Default
1.00%
Setting range
0.00%
~
100.00%
This function is used to limit the deviation between two PID outputs (2 ms per PID output) to suppress the
rapid change of PID output and stabilize the running of the AC drive.
PA-23 and PA-24 respectively correspond to the maximum absolute value of the output deviation in forward
direction and in reverse direction.
PA-25
PID integral property
Default
00
Setting range
Unit's
digit
Integral separated
0
Invalid
1
Valid
Ten's
digit
Whether to stop integral
operation when the output reaches the limit
0
Continue integral operation
1
Stop integral operation