HV580L Series Frequency Inverter
118
6
Motor overload
pre-warning
The AC drive judges whether the motor load exceeds the
overload pre-warning threshold before performing the
protection action. If the pre-warning threshold is
exceeded, the terminal becomes ON. For motor overload
parameters, see the descriptions of P9-00 to P9-02.
7
AC drive overload
pre-warning
The terminal becomes ON 10s before the AC drive
overload protection action is performed.
8
Set count value reached
The terminal becomes ON when the count value reaches
the value set in PB-08.
Value
Function
Description
9
Designated count
value reached
The terminal becomes ON when the count value reaches
the value set in PB-09.
10
Length reached
The terminal becomes ON when the detected actual
length exceeds the value set in PB-05
11
PLC cycle complete
When simple PLC completes one cycle, the terminal
outputs a pulse signal with width of 250 ms.
12
Accumulative running
time reached
If the accumulative running time of the AC drive exceeds
the time set in P8-17, the terminal becomes ON.
13
Frequency limited
If the set frequency exceeds the frequency upper limit or
lower limit and the output frequency of the AC drive
reaches the upper limit or lower limit, the terminal
becomes ON.
14
Torque limited
In speed control mode, if the output torque reaches the
torque limit, the AC drive enters the stall protection state
and meanwhile the terminal becomes ON.