HV580L Series Frequency Inverter
131
If the AC drive is in the stop state, the load speed is the speed corresponding to the set frequency, namely,
"set load speed". If the set frequency is 50.00 Hz, the load speed in the stop state is 50.00 x 2.000 = 100.00
(display of 2 decimal places).
P7-13
Accumulative power-on time
Default
-
Setting Range
0
~
65535 hour
It is used to display the accumulative power-on time of the AC drive since the delivery. If the time reaches the
set power-on time (P8-17), the terminal with the digital output function 24 becomes ON.
P7-14
Accumulative power consumption
Default
-
Setting Range
0
~
65535 kWh
It is used to display the accumulative power consumption of the AC drive until now.
Group P8 Auxiliary Functions
P8-00
JOG running frequency Default
2.00Hz
Setting Range
0.00Hz
~
maximum frequency
P8-01
JOG acceleration time
Default
20.0s
Setting Range
0.0s
~
6500.0s
P8-02
JOG deceleration time
Default
20.0s
Setting Range
0.0s
~
6500.0s
These parameters are used to define the set frequency and acceleration/deceleration time of the AC drive when jogging.
The startup mode is "Direct start" (P6-00 = 0) and the stop mode is "Decelerate to stop" (P6-10 = 0) during jogging.
P8-03
Acceleration time 2
Default
Model dependent
Setting Range
0. 0s
~
6500.0s
P8-04
Deceleration time 2
Default
Model dependent
Setting Range
0. 0s
~
6500.0s
P8-05
Acceleration time 3
Default
Model dependent
Setting Range
0. 0s
~
6500.0s
P8-06
Deceleration time 3
Default
Model dependent
Setting Range
0. 0s
~
6500.0s
P8-07
Acceleration time 4
Default
Model dependent
Setting Range
0. 0s
~
6500.0s
P8-08
Deceleration time 4
Default
Model dependent
Setting Range
0. 0s
~
500.0s
The HV580L provides a total of four groups of acceleration/deceleration time, that is, the preceding three groups
and the group defined by P0-17 and P0-18. Definitions of four groups are completely the same. You can switch