HV580L Series Frequency Inverter
140
If the output current of the AC drive is within the positive and negative amplitudes of any current reaching
detection value, the corresponding DO becomes ON.
The HV580L provides two groups of any current reaching detection parameters, including current detection
value and detection amplitudes, as shown in the following figure.
Figure 6-23 Any current reaching detection
P8-42
Timing function
Default
0
Setting Range
0
Disabled
1
Enabled
P8-43
Timing duration source Default
0
Setting Range
0
P8-44
1
VS
2
AS
3
VS2
(100% of analog input corresponds to the value of P8-44)
P8-44
Timing duration
Default
0.0Min
Setting Range
0.0Min
~
6500.0Min
These parameters are used to implement the AC drive timing function.
If P8-42 is set to 1, the AC drive starts to time at startup. When the set timing duration is reached, the AC drive
stops automatically and meanwhile the corresponding DO becomes ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration can be queried by U0-20.
The timing duration is set in P8-43 and P8-44, in unit of minute.
P8-45
VS input voltage lower limit
Default
3.10V
Setting Range
0.00V
~
P8-46
P8-46
VS input voltage upper limit
Default
6.80V
Setting Range
P8-45
~
10.00V
These two parameters are used to set the limits of the input voltage to provide protection on the AC drive.