HV580L Series Frequency Inverter
24
Type
Terminal
Name
Function Description
Digital input
X1- OP
Digital input1
Optical coupling isolation, compatible with dual polarity input
Impedance: 2.4 kΩ
Voltage range for level input: 9
–30 V
X2- OP
Digital input 2
X3- OP
Digital input 3
X4- OP
Digital input 4
X5- OP
High-speed
pulse
input
Besides features of X1
–X 4, it can be used for high-speed pulse input.
Maximum input frequency: 100 kHz
Analog
Output
AO1-GND Analog output 1
Voltage or current output is decided by jumper J5.
Output voltage range: 0
–10 V
Output current range: 0
–20 mA
Digital
output
Y1-CME
Digital
output 1
Optical coupling isolation, dual polarity open collector output
Output voltage range: 0
–24 V
Output current range: 0
–50 mA
Note that CME and COM are internally insulated, but they are shorted
by jumper externally. In this case DO1 is driven by +24 V by default. If
you want to drive DO1 by external power supply, remove the jumper.
Y2- COM
High-speed
pulse output
It is limited by P5-00 (Y2 terminal output mode selection).
As high-speed pulse output, the maximum frequency hits 100 kHz.
As open-collector output, its specification is the same as that of Y1
Relay output
T/A-T/B
NC terminal
Contact driving capacity:
250 VAC, 3 A, COS ø = 0.4
30 VDC, 1 A
T/A-T/C
NO terminal
Auxiliary
interface
J12
Extension card
interface
I28-pin terminal Connect to an optional card (I/O extension card, PLC
card and various bus cards)
J3
PG card
interface
Support various types of PG cards: OC, differential, UVW and resolver.
J7
External
operation
panel interface
Connect to external operation panel.