HV580L Series Frequency Inverter
121
7
VS
0V
~
10V
8
AS
0V
~
10V (Or 0
~
20mA)
9
VS2
0V
~
10V
10
Length
0
~
maximum set length
11
Count value
0
~
maximum count value
12
Communication setting
0.0%
~
100.0%
13
Motor rotational speed
0
~
rotational speed corresponding to maximum
output frequency
14
Output current
0.0A
~
1000.0A
15
Output voltage
0.0V
~
1000.0V
P5-09
Maximum Y2P output frequency Default
50.00kHz
Setting Range
0.01kHz
~
100.00kHz
If the Y2 terminal is used for pulse output, this parameter is used to set the maximum frequency of pulse output.
P5-10
AO1 offset coefficient
Default
0.0%
Setting Range
-100.0%
~
+100.0%
P5-11
AO1 gain
Default
1.00
Setting Range
-10.00
~
+10.00
P5-12
Expansion card AO2 offset coefficient Default
0.00%
Setting Range
-100.0%
~
+100.0%
P5-13
Expansion card AO2 gain
Default
1.00
Setting Range
-10.00
~
+10.00
These parameters are used to correct the zero drift of analog output and the output amplitude deviation. They
can also be used to define the desired AO curve.
If "b" represents zero offset, "k" represents gain, "Y" represents actual output, and "X" represents standard
output, the actual output is: Y = kX + b.
The zero offset coefficient 100% of AO1 and AO2 corresponds to 10 V (or 20 mA). The standard output refers
to the value corresponding to the analog output of 0 to 10 V (or 0 to 20 mA) with no zero offset or gain
adjustment.
For example, if the analog output is used as the running frequency, and it is expected that the output is 8 V
when the frequency is 0 and 3 V at the maximum frequency, the gain shall be set to -0.50, and the zero offset
shall be set to 80%.
P5-17
Y2R output delay time
Default
0.0s
Setting Range
0.0s
~
3600.0s
P5-18
RELAY1 output delay time
Default
0.0s
Setting Range
0.0s
~
3600.0s
P5-19
RELAY2 output delay time
Default
0.0s
Setting Range
0.0s
~
3600.0s