HV580L Series Frequency Inverter
8
5) Motor heat and noise
The output of the AC drive is pulse width modulation (PWM) wave with certain harmonic frequencies, and
therefore, the motor temperature, noise, and vibration are slightly greater than those when the AC drive runs
at power frequency (50 Hz).
6) When external voltage is out of rated voltage range
The AC drive must not be used outside the allowable voltage range specified in this manual. Otherwise, the AC
drive's components may be damaged. If required, use a corresponding voltage step-up or step-down device.
7) Contactor at the I/O terminal of the AC drive
When a contactor is installed between the input side of the AC drive and the power supply, the AC drive must
not be started or stopped by switching the contactor on or off. If the AC drive has to be operated by the
contactor, ensure that the time interval between switching is at least one hour since frequent charge and
discharge will shorten the service life of the capacitor inside the AC drive.
When a contactor is installed between the output side of the AC drive and the motor, do not turn off the
contactor when the AC drive is active. Otherwise, modules inside the AC drive may be damaged.
8) When external voltage is out of rated voltage range
The AC drive must not be used outside the allowable voltage range specified in this manual. Otherwise, the AC
drive's components may be damaged. If required, use a corresponding voltage step-up or step-down device.
9) Prohibition of three-phase input changed into two-phase input
Do not change the three-phase input of the AC drive into two-phase input. Otherwise, a fault will result or the
AC drive will be damaged.
10) Lightning shock protection
This series of frequency converter is equipped with a lightning over current protection device, for induction
lightning has certain ability of self-protection, but for frequent lightning place customers should also be adding
lightning protection devices in inverter front.
11) Altitude and de-rating
In places where the altitude is above 1000 m and the cooling effect reduces due to thin air, it is necessary to
de-rate the AC drive. Contact HNC Electric for technical support.
12) Some special usages
If wiring that is not described in this manual such as common DC bus is applied, contact the agent or HNC
Electric for technical support.
13) Disposal
The electrolytic capacitors on the main circuits and PCB may explode when they are burnt. Poisonous gas is