HV580L Series Frequency Inverter
138
If the output frequency of the AC drive is within the positive and negative amplitudes of the any frequency
reaching detection value, the corresponding DO becomes ON.
The HV580L provides two groups of any frequency reaching detection parameters, including frequency
detection value and detection amplitude, as shown in the following figure.
Figure 6-20 Any frequency reaching detection
P8-34
Zero current detection level
Default
5.0%
Setting Range
0.0%
~
300.0%( rated motor current)
P8-35
Zero current detection delay time
Default
0.10s
Setting Range
0.00s
~
600.00s
If the output current of the AC drive is equal to or less than the zero current detection level and the duration
exceeds the zero current detection delay time, the corresponding DO becomes ON. The zero current
detection is shown in the following figure.
Figure 6-21 Zero current detection