HV580L Series Frequency Inverter
137
Figure 6-19 Acceleration/deceleration time switchovers
During acceleration, if the running frequency is smaller than the value of P8-25, acceleration time 2 is selected.
If the running frequency is larger than the value of P8-25, acceleration time 1 is selected.
During deceleration, if the running frequency is larger than the value of P8-26, deceleration time 1 is selected.
If the running frequency is smaller than the value of P8-26, deceleration time 2 is selected.
P8-27
Terminal JOG preferred Default
0
Setting Range
0: Disabled; 1: Enabled
It is used to set whether terminal JOG is preferred.
If terminal JOG is preferred, the AC drive switches to terminal JOG running state when there is a terminal JOG
command during the running process of the AC drive.
P8-28
Frequency detection value (PDT2)
Default
50.00Hz
Setting Range
0.00Hz
~
maximum frequency
P8-29
Frequency detection hysteresis (FDT hysteresis 2) Default
5.0%
Setting Range
0.0%
~
100.0 % ( PDT2 level)
The frequency detection function is the same as FDT1 function. For details, refer to the descriptions of P8-19 and P8-20.
P8-30
Any frequency reaching detection value 1
Default
50.00Hz
Setting Range
0.00Hz
~
maximum frequency
P8-31
Any frequency reaching detection amplitude 1
Default
0.0%
Setting Range
0.0%
~
100.0%(maximum
frequency)
P8-32
Any frequency reaching detection value 2
Default
50.00Hz
Setting Range
0.00Hz
~
maximum frequency
P8-33
Any frequency reaching detection amplitude 2
Default
0.0%
Setting Range
0.0%
~
100.0%(maximum
Frequency)