HV580L Series Frequency Inverter
149
P9-56
Type of motor temperature sensor
Default
0
Setting Range
0
No temperature sensor
1
PT100
2
PT1000
P9-57
Motor overheat protection threshold Default
110
℃
Setting Range
0
℃~
200
℃
P9-58
Motor overheat warning threshold
Default
90
℃
Setting Range
0
℃~
200
℃
The signal of the motor temperature sensor needs to be connected to the optional I/O extension card. VS2 on
the extension card can be used for the temperature signal input.
The motor temperature sensor is connected to VS2 and PGND of the extension card. The VS2 terminal of the
HV580L supports both PT100 and PT1000. Set the sensor type correctly during the use. You can view the
motor temperature via C-34.
If the motor temperature exceeds the value set in P9-57, the AC drive reports an alarm and acts according to
the selected fault protection action.
If the motor temperature exceeds the value set in P9-58, the DO terminal on the AC drive allocated with
function 39 (Motor overheat warning) becomes ON.
P9-59
Action selection at instantaneous
power failure
Default
0
Setting Range
0
Invalid
1
Decelerate
2
Decelerate to stop
P9-60
Action pause judging voltage at
instantaneous power failure
Default
90.0%
Setting Range
80.0%
~
100.0%
P9-61
Voltage rally judging time at
instantaneous power failure
Default
0.50s
Setting Range
0.00s
~
100.00s