E6582062
11. Table of parameters
11-6
1
9
11
11. 3
Extended parameter
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
F100
0100
Low-speed signal
output frequency
0.0 - FH
Hz
0.0
Y
F101
0101
Reach signal
specified frequency
0.0 - FH
Hz
0.0
Y
F102
0102
Reach signal
detection band
0.0 - FH
Hz
2.5
Y
F105
0105
Fwd/Rev priority of
both close
0: Reverse
1: Stop
-
-
1
N
F107
0107
Terminal RX input
voltage select
0: 0 to +10 V
1: -10 to +10 V
-
-
0
N
[6. 2. 2]
[6. 6. 2]
[7. 3. 1]
[7. 3. 4]
F108
0108
Terminal RR input
select
1: Voltage input (0-10 V)
2: -
3: -
4: PTC input
5: PT100 (2-wire) input
6: -
7: PT1000 (2-wire) input
8: -
9: KTY84 input
-
-
1
N
F110
0110
Always active
function 1
0 - 177
*4
-
-
6
N