E6582062
5. [Fundamental operation] How to use parameters
5-74
4
5
9
(3)
Displaying frequency by converting to other unit
<F702: Free unit multiplication factor>
<F703: Target of free unit>
<F705: Free unit inclination polarity>
<F706: Free unit bias>
■
Function
The monitor display and the frequency display of parameters can be converted into the motor speed
or load speed.
The unit of the set value or that of feedback can be changed at PID control for easy setting.
■
Parameter setting
■
Reference of setting
The value obtained by multiplying the displayed frequency by the setting value of <F702: Free unit
multiplication factor> is displayed.
"Value displayed" = "Monitor-displayed" or "parameter-set frequency" x <F702>
■
Parameters converted with <702: Free unit multiplication factor>
When <F703: Target of free unit> is "0"
It applies to all the frequency.
• Frequency monitor display: Frequency command value, Output frequency, PID feedback value,
Stator frequency, During stop: Frequency command value (During run: Output frequency)
• Frequency-related parameters: <FC>, <FH>, <UL>, <LL>, <FPId>, <Sr0> - <Sr7>, <F100>,
<F101>, <F102>, <F190>, <F192>, <F194>, <F196>, <F198>, <F202>, <F204>, <F208>,
<F211>, <F213>, <F217>, <F219>, <F223>, <F225>, <F229>, <F231>, <F235>, <F237>,
<F240>, <F241>, <F242>, <F243>, <F244>, <F250>, <F260>, <F265>, <F267>, <F268>,
<F270> - <F275>, <F287> - <F294>, <F321>, <F322>, <F330>, <F331>, <F346>, <F350>,
<F352>, <F355>, <F364>, <F365>, <F367>, <F368>, <F370>, <F371>, <F374>, <F383>,
<F391> - <F393>, <F426>, <F428>, <F431>, <F432>, <F466>, <F505>, <F513>, <F517>,
<F606>, <F623>, <F624>, <F643>, <F649>, <F812>, <F814>, <F964> - <F979>
Title
Parameter name
Adjustment range
Unit
Default
setting
F702
Free unit multiplication
factor
0.00: Disabled
0.01 - 200.0
times
0.00
F703
Target of free unit
0: All frequencies
1: PID frequencies
-
0
F705
Free unit inclination
polarity
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
-
1
F706
Free unit bias
0.00 - FH
Hz
0.00
0.0Hz
STOP
15:37
Min: 0.00
Max: 200.00
X1000
X100
X10
X1
F702 :Free unit multiplying factor
0.00
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...