E6582062
11-63
11. Table of parameters
1
3
9
10
11
The function No. in the following table can be assigned to parameters <F130>, <F132>-<F134>,
<F137>, <F138>, and <F159>-<F163>.
11. 9
Output terminal function
Function Number
Symbol
Function
Action
Reference
Positive
logic
Negative
logic
0
1
LL
Lower limit frequency (LL) ON: Output frequency over <LL: Lower limit frequency>
2
3
UL
Upper limit frequency
(UL)
ON: Output frequency is <UL: Upper limit frequency> or more
4
5
LOW
Low-speed signal
ON: Output frequency is <F100: Low-speed signal output
frequency> or more
6
7
RCH
Acc/Dec completed
Output frequency is within command frequency ± <F102:
Reach signal detection band>
8
9
RCHF
Specified frequency
attainment
ON: Output frequency is within <F101: Reach signal
specified frequency> ± <F102: Reach signal detection band>
10
11
FL1
Failure signal 1
ON: Tripped
[6. 30. 5]
[6. 30. 6]
[6. 30. 7]
[6. 30. 8]
12
13
FL2
Failure signal 2
ON: At trip, except "EF", "OCL", "EPHO", and "OL2"
14
15
POC
Overcurrent (OC) pre-
alarm
ON: Output current is <F601: Stall prevention level 1> or
more
16
17
POLI
Inverter overload (OL1)
pre-alarm
ON: Calculated value of overload protection level is a specific
level or more
18
19
POLM
Motor overload (OL2)
pre-alarm
ON: Calculated value of overload protection level is <F657:
Overload alarm level> or more
20
21
POH
Overheat (OH) pre-alarm
ON: Approx. 95°C or more of IGBT element
OFF: Under approx. 95°C of IGBT element (90°C or less
after detection is turned on)
22
23
POP
Overvoltage (OP) pre-
alarm
ON: Overvoltage limit in operation
24
25
MOFF
Power circuit
undervoltage (MOFF)
alarm
ON: Main circuit undervoltage (MOFF) detected
26
27
UC
Undercurrent (UC) alarm
ON: When the output current falls below the value set by
<F611: Undercurrent detection level> and remains below
<F611: Undercurrent detection level>
+
<F609: Undercurrent
detection hysteresis> for the period of time specified by
<F612: Undercurrent detection time>
OFF: Output current is over <F611> (<F611>+<F609> or
more after detection turns on)
28
29
OT
Overtorque (OT) alarm
ON: When the torque becomes <F616: Overtorque detection
level during power running> or more, and remains over
<F616: Overtorque detection level during power running> -
<F619: Overtorque detection hysteresis> for the time
specified by <F618: Overtorque detection time>
OFF: Torque is under <F616> (<F616>-<F619> or less after
detection turns on)
30
31
POLR
Braking resistor overload
(OLr) pre-alarm
ON: 50% or more of calculated value of <F309: Braking
resistor capacity> set overload protection level
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...