E6582062
13-5
13. Trip information and measures
I
II
III
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Etn
0028
Auto-tuning
error
1) The motor parameter does not match
the motor characteristic.
2) Executed auto-tuning while the motor is
rotating.
3) The output frequency does not increase
within few minutes.
1) Set the motor parameters according to
the motor characteristic.
<vL: Base frequency 1>,
<vLv: Base frequency voltage>,
<F405: Motor rated capacity>,
<F415: Motor rated current>,
<F417: Motor rated speed>, etc.
2) Check that the motor is stopped, and
perform auto-tuning again.
3) Check that the motor is not stopped
while the output frequency is risin on
the system.
Etn1
0054
Auto-tuning
error 1
1) The motor is not connected.
2) Something other than the motor is
connected.
3) In the induction motor, an improper
value, a synchronized motor speed
value or a value close to it is set in
<F417: Motor rated speed>.
1) and 2) Check that the motor is
connected.
3) Set <F417> according to the motor
rating.
Etn2
0055
Auto-tuning
error 2
The motor parameter does not match the
motor characteristic.
Set the motor parameters according to the
motor characteristic.
<vL: Base frequency 1>,
<vLv: Base frequency voltage>,
<F405: Motor rated capacity>,
<F415: Motor rated current>,
<F417: Motor rated speed>, etc.
Etn3
0056
Auto-tuning
error 3
The setting on <vL: Base frequency 1> or
<F417: Motor rated speed> does not
match the motor rating.
Set <vL: Base frequency 1> or <F417:
Motor rated speed> according to the
motor rating.
EtyP
0029
Inverter type
error
1) Internal error exists.
2) Replaced the printed circuit board
(contact your Toshiba distributor for
replacing the printed circuit board).
1) Error in internal inverter.
Contact your Toshiba distributor.
2) Set <tyP: Default setting> = "6: Initialize
typeform".
OC1
0001
Overcurrent
(during
acceleration)
1) The acceleration time is short.
2) <Pt: V/f Pattern> does not match the
machinery.
3) Momentary power failure occurred, and
tried to start the rotating motor.
4) Tried to run the special motor
(impedance small).
5) Tried to run a low inductance motor like
a high-speed motor.
6) When <Pt> = "11", polarity of PG is
opposite.
7) When <F614: Pulse width of short
circuit detection at start> = "0", and
<F613>=2, or 3, inverter output short
circuit.
1) Increase the acceleration time. <ACC:
Acceleration time 1>, etc.
2) Set <Pt: V/f Pattern> according to the
machinery.
3) Set <F301: Auto-restart>. Depending
on the characteristic of machinery,
<F302: Regenerative power ride-
through> = "1" is also effective.
4) When <Pt> is set to "0", "1", "2", or "7",
lower <vb: Manual torque boost 1>.
For settings other than "0", "1", "2", or
"7", perform auto-tuning with <F400:
Offline auto-tuning>. <F402: Automatic
torque boost> is set matching the
motor.
5) Change the inverter to large capacity.
OC2
0002
Overcurrent
(during
deceleration)
1) The deceleration time is short.
2) Tried to run a low inductance motor like
a high-speed motor.
3) When <Pt> = "11", polarity of PG is
opposite.
4) When <F614: Pulse width of short
circuit detection at start> = "0", and
<F613>=2, or 3 inverter output short
circuit.
1) Increase the deceleration time. <dEC:
Deceleration time 1>, etc.
2) Change the inverter to large capacity.
*Enable/Disable can be selected for trip with a parameter.
Trip
display
Failure
code
Trip name
Detection factor
Measures
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...