E6582062
6-185
6. [Advanced] How to use parameters
3
4
6
9
■
Parameter setting
Title
Parameter name
Adjustment range
Unit
Default setting
F800
RS485 (1) baud rate
*1
0: 9600 bps
1: 19200 bps
2: 38400 bps
1
F801
RS485 (1) parity
0: Disabled
1: Even parity
2: Odd parity
1
F802
Inverter number
(RS485 common)
0 - 247
0
F803
RS485 (1) time-out time
*2
0.0: Disabled
0.1 - 100.0
s
0.0
F804
RS485 (1) time-out
operation
1: Continue running
2, 3: -
4: Trip
5: -
6: Trip after deceleration stop
0
F805
RS485 (1) transmission
wait time
0.00 - 2.00
s
0.00
F806
RS485 (1) inverter to
inverter communication
0: Follower (0Hz command when Leader
fails)
1: Follower (continue running when Leader
fails)
2: Follower (emergency off when Leader
fails)
3: Leader (transmit frequency command)
4: Leader (transmit output frequency signal)
5: Leader (transmit torque command)
6: Leader (transmit output torque command)
0
F807
RS485 (1) protocol
0: TOSHIBA
1: MODBUS
0
F808
RS485 (1) time-out
detection
0: Always
1: Run command and frequency command
by communication are enabled.
2: During run by communication
1
F809
Operation panel
connection priority
*3
0: By the parameter setting
1: Connect to connector 1
2: Connect to connector 2
1
F810
Communication
frequency point select
0: Disabled
1: RS485 (1)
2: RS485 (2)
3: Communication option
4: Embedded Ethernet
0
F811
Communication point 1
input value
0-100
%
0
F812
Communication point 1
frequency
0.0-FH
Hz
0.0
F813
Communication point 2
input value
0-100
%
100
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...