E6582062
11-39
11. Table of parameters
1
3
9
10
11
F730
0730
Panel frequency
setting lockout
0: Unlocked without
press OK
1: Locked
2: Unlocked after press
OK
-
-
2
Y
F731
0731
Operation after
disconnection
detection during
panel run
1: Continue running
2 - 3: -
4: Trip
-
-
4
Y
F732
0732
Panel Hand/Auto
function lockout
0: Unlocked
1: Locked
-
-
1
Y
F733
0733
Panel Run lockout
0: Unlocked
1: Locked
-
-
0
Y
F734
0734
Panel emergency
off lockout
0: Unlocked
1: Locked
-
-
0
Y
F735
0735
Panel reset lockout
0: Unlocked
1: Locked
-
-
0
Y
F736
0736
CMOd/FMOd
change lockout
during run
0: Unlocked
1: Locked
-
-
1
Y
F737
0737
Panel keys lockout
0: Unlocked
1: Locked
2: Locked only
extension panel
3: Locked only operation
panel
-
-
0
Y
F738
0738
Password setting
0: Disabled
1 - 9998
9999: Password was set
-
-
0
Y
F739
0739
Password
verification
0: non-setting
1 - 9998
9999: Password was set
-
-
0
Y
F740
0740
Trace
0: Disabled
1: At trip
2: At trigger input
3: At trip & at trigger
input
-
-
1
Y
F741
0741
Trace cycle
0: 4ms
1: 20ms
2: 100ms
3: 1s
4: 10s
-
-
2
Y
F742
0742
Trace data 1
0 - 162
*3
-
-
0
Y
F743
0743
Trace data 2
-
-
1
Y
F744
0744
Trace data 3
-
-
2
Y
F745
0745
Trace data 4
-
-
3
Y
F748
0748
Cumulative power
save
0: Disabled
1: Enabled
-
-
0
Y
F749
0749
Cumulative power
unit
0: 1.0=1 kWh
1: 1.0=10 kWh
2: 1.0=100 kWh
3: 1.0=1000 kWh
4: 1.0=10000 kWh
5: 1.0=100000 kWh
-
-
*1
Y
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...