6. [Advanced] How to use parameters
3
4
6
9
When the inverter starts to run, the sleep function works after the output frequency is over the value
of <LL: Lower limit frequency>.
Also, when it starts, this function enables you to automatically stop the inverter after the period set
with <F259: Run sleep detection time at startup> if the output frequency does not increase to the
value of <LL> due to a load error. However, if the output frequency is over the value of <LL>, the
function of <F259> is invalid until the run signal is turned OFF
For non-PID control, this function is canceled when the frequency command value is over the values
of <LL: Lower limit frequency> and <F391: Sleep detection hysteresis> (Hz) or when the run
command is turned OFF.
For PID control, set values with <F392: Wakeup deviation> and <F393: Wakeup feedback>.
For details, refer to the PID control instruction manual (E6582112).
This function is also valid when you switch between forward and reverse run.
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]