E6582062
5. [Fundamental operation] How to use parameters
5-54
4
5
9
5. 3. 8
Setting PID control
<FPld: PID1 set value>
■
Function
This parameter is applied to process control including keeping airflow, pressure, and the amount of
flow constant.
The set value and the feedback signal (4 - 20 mA, 0 - 10 V) from the detector are compared, and the
frequency is changed toward the set value.
■
Parameter setting
■
Reference of setting
1) Selecting set value and feedback input
Set the set value of PID control with <F389: PID1 set value select> and the feedback input
value with <F360: PID1 feedback input select>.
• For <F389>, do not set the signal used for <F360>.
• When the feedback value and the set value match, the signal can be output. Assign function
"144: PID 1, 2 frequency command agreement" to the output terminals.
Title
Parameter name
Adjustment range
Unit
Default setting
FPId
PID1 set value
F368 to F367
Hz
0.0
0.0Hz
STOP
15:27
Min: 0.0
Max: 60.0
X1000
X100
X10
X1
Hz
FPld :PlD1 set value
0.0
Basic parameter