10
■
Wire size for ND rating
Voltage
class
Applicable
motor (kW)
Inverter type-form
Wire size (mm
2
)
Power circuit
DC wire
Braking
resistor
(Optional)
Grounding
wire
Input
Output
3-phase
240 V
0.75
VFAS3-
2004P
1.5
1.5
2.5
1.5
2.5
1.5
2007P
1.5
1.5
2.5
1.5
2.5
2.2
2015P
1.5
1.5
2.5
1.5
2.5
4.0
2022P
2.5
4
2.5
1.5
4
5.5
2037P
4
6
4
1.5
6
7.5
2055P
6
10
6
2.5
10
11
2075P
10
16
10
4
16
15
2110P
16
25
16
6
16
18.5
2150P
25
35
25
10
16
22
2185P
35
50
35
16
25
30
2220P
50
70
50
25
35
37
2300P
70
95
70
35
50
45
2370P
95
120
95
50
70
55
2450P
70x2
70x2
50x2
50
95
75
2550P
95x2
95x2
70x2
70
120
3-phase
480 V
0.75
VFAS3-
4004PC
1.5
1.5
2.5
1.5
2.5
1.5
4007PC
1.5
1.5
2.5
1.5
2.5
2.2
4015PC
1.5
1.5
2.5
1.5
2.5
4.0
4022PC
1.5
1.5
2.5
1.5
2.5
5.5
4037PC
1.5
2.5
2.5
1.5
2.5
7.5
4055PC
2.5
4
2.5
1.5
2.5
11
4075PC
4
6
4
1.5
4
15
4110PC
6
10
6
2.5
10
18.5
4150PC
10
10
10
2.5
10
22
4185PC
10
16
10
4
16
30
4220PC
16
25
16
6
16
37
4300PC
25
35
25
10
16
45
4370PC
35
35
35
16
16
55
4450PC
50
50
50
16
25
75
4550PC
70
95
70
35
50
90
4750PC
95
120
95
35
70
110
4900PC
50x2
50x2
70x2
35
95
132
4110KPC
70x2
70x2
70x2
50
95
160
4132KPC
95x2
95x2
95x2
70
120
220
4160KPC
150x2
150x2
150x2
95
150
250
4200KPC
150x2
150x2
185x2
150
150
280
4220KPC
150x3
120x3
150x3
150
120x2
315
4280KPC
150x3
150x3
150x3
150
120x2
Memo
• The wire size of this chapter comply with IEC60364-5-52 (Grounding wire: IEC60364-5-54). It
does not comply with UL Standard.
• For the wire size to comply with UL Standard, refer to [9. 2. 3].
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...