E6582062
5. [Fundamental operation] How to use parameters
5-16
4
5
9
■
Setting a time before the trip of the electronic thermal occurs: <F607: Motor
overload time>
Setting a time before the trip of the electronic thermal occurs: <F607: Motor overload time>
Set a time before the overload trip "OL2" occurs at the motor overload of 150%.
■
Selecting how to detect inverter overload: <F631: Inverter overload detection>
This function enables to automatically increase the continuous output current and the inverter
overload capacity when the ambient temperature is low.
Title
Parameter name
Adjustment range
Unit
Default
setting
F607
Motor overload time
10 - 2400
s
300
Monitored output current
(%)
Motor overload time (s) (Outline data)
tHrA=100
tHrA=50
F607=600 is set
F607=300 is set
F606 or
more
0.01 Hz
F606 or
more
0.01 Hz
68
34
-
7200
-
3600
70
35
-
3600
-
1800
80
40
-
1000
-
500
90
45
-
600
-
300
100
50
-
420
-
210
112
56
12000
310
6000
155
120
60
2400
270
1200
135
130
65
1200
230
600
115
140
70
800
190
400
95
150
75
600
170
300
85
200
100
270
110
135
55
Output frequency
0.01Hz *1
*1 Except when
Output frequency
<F606> or more
Motor overload time (s)
Monitored output current (%)
x1.1
0
x0.6
x1.5
Motor overload protection characteristics
<F606>=0 and 0.01 Hz
<F607>
<tHrA>
<tHrA>
<tHrA>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...