E6582062
5-67
5. [Fundamental operation] How to use parameters
3
4
5
9
5. 4. 2
Restarting smoothly after momentary power failure
<F301: Auto-restart>
■
Function
The motor that is coasting due to momentary power failure is accelerated immediately after the
power is restored (auto-restart function).
In addition, this parameter detects the motor speed and direction of rotation of the motor during
coasting at the time of startup, and allows switching from commercial power operation to inverter
operation without stopping the motor(motor speed search function).
■
Parameter setting
■
Selecting a setting value
1: Power failure
The motor that is coasting due to momentary power failure is accelerated immediately after the
power is restored.
It is operated after power is restored after power circuit undervoltage is detected. Turn on the run
command.
CAUTION
Mandatory
action
• When the auto-restart after momentary stop function is selected, stand clear of motors and
• Attach caution labels indicating functions programmed for Auto restart, on inverters, motors and
machines.
Please prevent accidents with the caution labels.
Title
Parameter name
Adjustment range
Default
setting
F301
Auto-restart
0: Disabled
1: Power failure
2: Terminal ST On/Off
3: Terminal ST On/Off or power failure
4: At startup
0
0.0Hz
STOP
15:35
F301 : Auto-restart
0: Disabled
1: Power failure
2: Terminal ST On/Off
3: ST On/Off or power failure
4: At startup
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...