E6582062
6-153
6. [Advanced] How to use parameters
3
4
6
9
6. 30. 22 Setting cumulative overcurrent level and time
<F659: Cumulative overcurrent level>
■
Function
Inverter cumulates the time when motor current is over this parameter. This cumulative time can be
confirmed in [Monitor mode].
■
Parameter setting
■
Signal output of the cumulative overcurrent time
You can confirm the cumulative overcurrent time in [Monitor mode].
Set the monitor numbers shown below to <F711: Monitor mode 1 display> to <F718: Monitor mode
8 display>. For details, refer to [8. 1. 1].
"93: Cumulative overcurrent time"
Title
Parameter name
Adjustment range
Unit
Default setting
F659
Cumulative overcurrent
level
10 - 200
%
100
Memo
• Cumulative overcurrent time can be confirmed in [Monitor mode]. You can reset the monitor
value to 0 with the setting of "15: Clear cumulative overcurrent time " in <tyP: Default setting>.
For details, refer to [5. 2. 9].
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
0.0Hz
STOP
14:06
F659 : Cumulative overcurrent level
Min: 10
Max: 200
X1000
X100
X10
X1
%
100
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...