E6582062
11. Table of parameters
11-46
1
9
11
F899
0899
Communication
option reset
0: -
1: Reset option and
inverter
-
-
0
N
F907
0907
PM regenerative
over-flux upper limit
0 - 150
%
50
N
-
F908
0908
PM no load current
0 - 100
%
0
N
-
F909
0909
PM step-out
detection frequency
rate
0 - 100
%
0
N
-
F910
0910
PM step-out
detection current
level
1 - 150
%
100
N
F911
0911
PM step-out
detection time
0.00: Disabled
0.01 - 2.55
s
0.00
N
F912
0912
PM q-axis
inductance
0.01 - 650.0
mH
10.00
N
F913
0913
PM d-axis
inductance
0.01 - 650.0
mH
10.00
N
F914
0914
Parameter for
manufacturer
-
-
-
-
-
-
F915
0915
PM control method
0: Method 0
1: Method 1
2: Method 2
3: Method 3
4: Method 4
-
-
3
N
F916
0916
PM starting current
0 - 100
%
25
N
-
F917
0917
IPM maximum
torque control
0: Disabled
1: Enabled
-
0
Y
-
F918
0918
IPM current phase
adjustment
-45.0 to +45.0
°C
0.0
Y
-
F919
0919
Parameter for
manufacturer
-
-
-
-
-
-
F920
0920
Parameter for
manufacturer
-
-
-
-
-
-
F921
0921
SPM initial position
estimation current
10 - 150
%
100
N
-
F922
0922
PM HF control
speed estimation
response
5 - 80
Hz
15
N
-
F923
0923
PM control
switching speed
5 - 100
%
25
N
-
F924
0924
PM speed
estimation filter
cutoff frequency
1 - 80
Hz
30
N
-
F925
0925
PM HF control
speed estimation
stabilization
coefficient
0.50 - 2.50
1.00
N
-
F926
0926
PM HF control
harmonic
frequency
100 - 1000
Hz
500
N
-
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...