6. [Advanced] How to use parameters
6-28
4
4
6
9
■
Guideline for the setting
When you want to use the terminal [S4], set <F146: Terminal S4 input select> to "1: Pulse train
input". When you want to use the terminal [S5], set <F147: Terminal S5 input select> to "1: Pulse
train input".
Set the number of pulses per 1 Hz of output frequency at <F378; Pulse train input pulses number>.
The minimum number of pulses that can be input to the terminals [S4] and [S5] is 10 pps, and the
maximum number of pulses 30 kpps. The duty is 50 ±10%.
The maximum frequency that can be output is 200 Hz.
■
Setting example
<F378> setting value
Input signal
Output frequency
25 (pps)
25 (pps)
1.0 (Hz)
100 (pps)
4.0 (Hz)
2k (pps)
80.0 (Hz)
50 (pps)
50 (pps)
1.0 (Hz)
100 (pps)
2.0 (Hz)
2k (pps)
40.0 (Hz)
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
• Details on operation by external signals -> Refer to [Chapter 7].
For use as PG feedback, refer to "Digital Encoder Instruction manual" (E6582148).
• Pulse train must be input after F146 or F147 is set to 1.
If pulse train is input when F146 or F147 is set to 0 (default value), preset speed works.
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...