E6582062
11. Table of parameters
11-32
1
9
11
F609
0609
Undercurrent
detection hysteresis
1 - 20
%
10
Y
F610
0610
Undercurrent trip
0: Disabled
1: Enabled
-
-
0
Y
F611
0611
Undercurrent
detection level
0 - 150
%
0
Y
F612
0612
Undercurrent
detection time
0 - 255
s
0
Y
F613
0613
Short circuit
detection at start
0: At every startup by
standard pulse
1: Only one time after
power on by standard
pulse
2: At every startup by
F614 setting pulse
3: Only one time after
power on by F614
setting pulse
-
-
0
N
F614
0614
Pulse width of short
circuit detection at
start
0: No short circuit
detection at start
1 - 50
μ
s
25
N
F615
0615
Overtorque trip
0: Disabled
1: Enabled
-
-
0
Y
F616
0616
Overtorque
detection level
during power
running
0: Disabled
1 - 320
%
150
Y
F617
0617
Overtorque
detection level
during regen
0: Disabled
1 - 320
%
150
Y
F618
0618
Overtorque
detection time
0.0 - 10.0
s
0.5
Y
F619
0619
Overtorque
detection hysteresis
0 - 100
%
10
Y
F620
0620
Cooling fan control
0: Auto ON/OFF, No
failure detection
1: Always ON, No failure
detection
2: Auto ON/OFF, Failure
detection
3: Always ON, Failure
detection
4 - 7: -
-
-
2
Y
F621
0621
Cumulative run time
alarm
0.0 - 999.0
100 h
876.0
Y
F622
0622
Abnormal speed
detection time
0.01 - 100.0
s
0.01
Y
F623
0623
Abnormal speed
increase band
0.00: Disabled
0.01 - 30.0
Hz
0.00
Y
F624
0624
Abnormal speed
decrease band
0.00: Disabled
0.01 - 30.0
Hz
0.00
Y
F625
0625
Undervoltage
detection level
50 - 79
80: Auto
%
80
N
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...