6. [Advanced] How to use parameters
6-130
4
4
6
9
6. 30. 8 Overtorque detection
<F615: Overtorque trip>
<F616: Overtorque detection level during power run-
ning>
<F617: Overtorque detection level during regen>
<F618: Overtorque detection time>
<F619: Overtorque detection hysteresis>
■
Function
The power running torque value is <F616: Overtorque detection level during power running> or
more, or the regen torque value is <F617: Overtorque detection level during regen> or more, and
remains over for the time specified by <F618: Overtorque detection time>, tripping or alarm can be
output. You can enable or disable the trip setting by <F615: Overtorque trip>. The trip display is "Ot".
■
Parameter setting
■
Difference depending on the setting of <F615: Overtorque trip>
0: Disabled
A trip does not occur. (Failure signal FL disabled)
Overtorque (OT) alarm can be output when the power running torque value is <F616> or more, or
the regen torque value is <F617> or more, is detected for the period of time specified by <F618>.
Title
Parameter name
Adjustment range
Unit
Default setting
F615
Overtorque trip
0: Disabled
1: Enabled
0
F616
Overtorque detection
level during power
running
0: Disabled
*1
1 - 320
*1 You can output an alarm set regardless of the <F615> setting. Trip or alarm cannot be output
when <F616> or <F617> is set to "0: Disabled".
%
150
F617
Overtorque detection
level during regen
1 - 320
%
150
F618
Overtorque detection
time
0.0-10.0
*2
*2 <F618>= "0.0" seconds is the shortest time detected on control.
s
0.5
F619
Overtorque detection
hysteresis
0 - 100
%
10
0.0Hz
STOP
13:55
F615 : Overtorque trip
0: Disabled
1: Enabled
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...