Making the motor standstill with PG feedback
control
<F255: 0Hz command select at stop>
<F250: DC braking frequency>
<F252: DC braking time>
■
Function
This function works only for the speed control of PG feedback control. Use a way other than DC
braking to make the motor standstill.
When this function is set, the inverter outputs a 0 Hz command instead of applying DC braking when
stopping to make the motor standstill for the specified time.
■
Parameter setting
■
How to select a setting value
0: DC braking
This function works as the DC braking function described in [6. 8. 1].
1: 0 Hz command
This function works only for the speed control of PG feedback control.
The inverter outputs 0 Hz for the period set with <F252: DC braking time> when the frequency
reaches the setting value of <F250: DC braking frequency>.
It does not work when <F250: DC braking frequency> is set to "0.0".
With this function enabled, <F254: Motor shaft fixing control> cannot be used.
■
How to use
This function is used for PG feedback control (<Pt: V/f Pattern> = "10", "11").
You should set the terminals [S4] and [S5] or have any option for PG feedback.
The normal DC braking action (the same action set with <F255> = "0") is performed for non-PG
feedback control.
Title
Parameter name
Adjustment range
Unit
Default setting
F255
0Hz command select at
stop
0: DC braking
1: 0 Hz command
0
F250
DC braking frequency
0.0 - FH
Hz
0.0
F252
DC braking time
0.0 - 25.5
s
1.0
0: Dc braking
1: 0Hz command
0.0Hz
STOP
13:09
F255 : 0Hz command at stop
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...