E6582062
5-9
5. [Fundamental operation] How to use parameters
3
4
5
9
5. 2. 3
Setting the output frequency limit
(1)
Setting the maximum frequency of the inverter
<FH: Maximum frequency>
■
Function
Set the maximum value of the frequency output from the inverter.
This frequency is also the criteria of acceleration and deceleration time.
■
Parameter setting
■
Guideline for the setting
Set the maximum frequency suited for the rating of the motor and load.
Title
Parameter name
Adjustment range
Unit
Default
setting
FH
Maximum frequency
30.0 - 590.0
Hz
80.0
*1
*1 Depending on the setup menu. Refer to [5. 3. 10].
The value of <FH> should be equal or greater than that of <VL>.
Memo
• Set <FH: Maximum frequency> after stopping the inverter. You cannot set it during run.
• When increasing the value of <FH: Maximum frequency>, you should also set the corresponding
value of <UL: Upper limit frequency> as required. --> Refer to the following "Setting the upper
and lower limits of the output frequency".
0.0Hz
STOP
15:08
Min: 30.0
Max: 590.0
X1000
X100
X10
X1
Hz
FH :Maximum frequency
80.0
Basic parameter
100%
80 Hz
60 Hz
Output frequency (Hz)
0
Frequency command
signal (%)
When <FH> = 80 Hz
When <FH> = 60 Hz
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...