E6582062
6-105
6. [Advanced] How to use parameters
3
4
6
9
6. 25. 3 Selecting tension control torque bias input and load
sharing gain input
<F423: Tension control torque bias input>
<F424: Load sharing gain input>
<F727: Panel tension torque bias>
<F728: Panel load sharing gain>
■
Function
These parameters are used to select tension control torque bias input and load sharing gain input.
■
Parameter setting
Title
Parameter name
Adjustment range
Unit
Default setting
F423
Tension control torque
bias input
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11: -
12: F727
13 - 19: -
20: Embedded Ethernet
21: RS485 communication connector 1
22: RS485 communication connector 2
23: Communication option
0
F424
Load sharing gain input
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11: -
12: F728
13 - 19: -
20: Embedded Ethernet
21: RS485 communication connector 1
22: RS485 communication connector 2
23: Communication option
0
F727
Panel tension torque bias
-250 to +250
%
0
F728
Panel load sharing gain
0 - 250
%
100
0.0Hz
STOP
13:42
F727 : Panel tension torque bias
Min: -250
Max: 250
X1000
X100
X10
X1
%
+0
Load sharing gain
᳒
Torque reference
Torque command
Tension control torque bias
Ქ
Ქ
Ქ
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...