E6582062
6. [Advanced] How to use parameters
6-154
4
4
6
9
<F650: Forced run>
■
Function
With the forced run control, the motor runs at the specified speed in an emergency.
■
Parameter setting
■
Setting the parameters and input terminal
Set <F650: forced run> = "1: Enabled"
Set any of the function to the unused input terminal. For details, refer to [7. 2. 1].
You can perform the forced run or fire speed run with the setting of <F650> = "1" and an assigned
input terminal is ON.
"56: Forced run"
• Once the input signal is ON, it is self-retained. The motor runs at the frequency set by
<F294>.
• In case of a slight failure, the motor performs the forced run, in which the operation is continued.
"58: Fire speed run"
• Once the input signal is ON, it is self-retained. The motor performs the fire speed run at the
frequency set by <F294>.
In both cases, to stop the running, the power circuit needs to be turned off.
During the forced run and the fire speed run, "FIrE" is displayed.
■
Signal output of forced run
Assign any of these to the unused output terminal. For details, refer to [7. 2. 2].
"138: During forced run"
"140: During fire speed run"
6. 31 Forced run control in emergency
Title
Parameter name
Adjustment range
Unit
Default setting
F650
Forced run
0: Disabled
1: Enabled
0
F294
Preset speed 15 / Forced
run speed
LL - UL
Hz
0.0
0.0Hz
STOP
14:07
F650 : Forced run
0: Disabled
1: Enabled
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...