E6582062
6. [Advanced] How to use parameters
6-36
4
4
6
9
6. 8. 1
Obtaining large torque with DC braking
<F249: DC braking carrier frequency>
<F250: DC braking frequency>
<F251: DC braking amount>
<F252: DC braking time>
<F253: Fwd/Rev DC braking priority>
■
Function
Apply direct current to the motor to obtain braking torque. This will stop the motor. It is used, for
example, to securely decelerate and stop the motor.
You can set the amount and time of direct current applied to the motor and the start frequency.
■
Parameter setting
6. 8
DC braking
Title
Parameter name
Adjustment range
Unit
Default setting
F249
DC braking carrier
frequency
1.0 - 16.0
kHz
*1
*1 Depending on capacity. For details, refer to [11. 6].
F250
DC braking frequency
0.0 - FH
Hz
0.0
F251
DC braking current
0 - 100
%
50
F252
DC braking time
0.0 - 25.5
s
1.0
F253
Fwd/Rev DC braking
priority
0: Disabled
1: Enabled
0