11. Table of parameters
11-42
1
9
11
F800
0800
RS485 (1) baud
rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: -
-
-
1
Y
F801
0801
RS485 (1) parity
0: Disabled
1: Even parity
2: Odd parity
-
-
1
Y
F802
0802
Inverter number
(RS485 common)
0 - 247
-
-
0
Y
F803
0803
RS485 (1) time-out
time
0.0: Disabled
0.1 - 100.0
s
0.0
Y
F804
0804
RS485 (1) time-out
operation
1: Continue running
2, 3: -
4: Trip
5: -
6: Trip after deceleration
stop
-
-
1
Y
F805
0805
RS485 (1)
transmission wait
time
0.00 - 2.00
s
0.00
Y
F806
0806
RS485 (1) inverter
to inverter
communication
0: Follower (0Hz
command when
Leader fails)
1: Follower (continue
running when Leader
fails)
2: Follower (emergency
off when Leader fails)
3: Leader (transmit
frequency command)
4: Leader (transmit
output frequency
signal)
5: Leader (transmit
torque command)
6: Leader (transmit
output torque)
-
-
0
Y
F807
0807
RS485 (1) protocol
0: TOSHIBA
1: MODBUS
-
-
0
Y
F808
0808
RS485 (1) time-out
detection
0: Always
1: Run command and
frequency command
by communication are
enabled.
2: During run by
communication
-
-
1
Y
F809
0809
Operation panel
connection priority
0: By the parameter
setting
1: Connect to conector 1
2: Connect to conector 2
-
-
1
Y
-
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...