The inverter can be reset with the following four methods after a trip occurs.
(1)
Panel operation
You can reset from the operation panel even if terminal run or communication run is per-
formed when the trip occurs.
The following is the reset procedure.
1
Press the [STOP/RESET] key with the trip dis-
played.
"CLr" blinks in the main area, and "Trip reset?
(STOP-Key)" is displayed on the lower side.
• The backlight is red.
(It is white when the setting of the backlight is
changed.)
2
When you press the [STOP/RESET] key again while "CLr" is blinking, the trip is reset.
The display on the screen once disappears, and the screen immediately after power on is dis-
played.
The backlight returns to while.
(2)
Terminal input (external signal)
Short the terminal [RES] and then open.
The inverter is reset when the terminal is opened.
In the default setting, the function "8: Reset 1" is assigned to the terminal [RES].
To reset with other input terminal, assignment of the reset function is required.
(3)
Communication
For details, refer to "RS485 Communication Function Instruction Manual" (E6582143).
(4)
Turning off power
Turn OFF the power and then turn it ON again.
When the power is off, some contents of the monitor at the time of the trip are lost.
13. 2 How to reset trip
Important
• Reset the inverter that has tripped after eliminating the cause of the trip.
If it is not eliminated, the inverter will trip again even after reset. Pay enough attention.
Copy
0.0Hz
TRIP
13:13
Monitor
Top View Mode
CLr
Trip reset ? (STOP-Key)
Easy
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...