E6582062
2-7
2. Installation and wiring
2
3
9
10
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface
quantity when operating in a sealed cabinet depending on motor capacity are as follows.
<ND rating>
Input
voltage
Class
Applicable
motor
capacity
(kW)
Inverter type-form
Frame
size
Inverter
calorific value
(W) *1
Inner side
calorific value
(W) *1
Forced
air-cooled
Required
ventilation
amount
(m
3
/min)
Sealeded
cabinet
Necessary
heat discharge
surface
quantity (m
2
)
3-phase
240 V
0.75
VFAS3-
2004P
A1
65
27
0.37
1.30
1.5
2007P
92
29
0.52
1.83
2.2
2015P
115
32
0.65
2.31
4.0
2022P
189
38
1.07
3.79
5.5
2037P
A2
243
47
1.38
4.85
7.5
2055P
A3
392
53
2.22
7.84
11
2075P
544
62
3.09
10.87
15
2110P
A4
625
90
3.55
12.51
18.5
2150P
750
101
4.26
15.01
22
2185P
874
112
4.96
17.49
30
2220P
A5
1084
136
6.15
21.68
37
2300P
1384
163
7.86
27.68
45
2370P
1631
184
9.26
32.63
55
2450P
A6
2466
278
14.00
49.33
75
2550P
3432
359
19.48
68.64
*1 Case of 100% load ND continuous operation. The heat loss for the optional external devices (input reactor, radio noise reduction filters, etc.) is not
included in the calorific values in the table.
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...