7. Operating using external signals
7-4
4
4
4
7
9
■
Connecting methods
1) A contact input (for sink logic)
2) Transistor output connection (for sink logic)
You can connect the input terminal and the terminal [CC] (common) to the programmable
controller output (non-logic switch) for control purposes. Use this connecting method for
forward/reverse run, or preset speed operation, etc.
■
Usage example: 3-wire operation (one-push operation)
The use of the 3-wire operation function allows the one-push signal (reset logic signal) to be self-
held during operation. No external sequence circuit is needed.
To perform 3-wire operation, make setting as shown below:
<F110: Always active function 1> = "6: Standby"
<CMOd: Run command select> = "0: Terminal"
<F111: Terminal F function 1> = "2: Fwd run" (default setting)
<F112: Terminal R function 1> = "4: Rev run"(default setting)
Also, assign "50: 3-wire operation hold/stop" ("51" for inversion input) to the input terminal.
The following shows an example for assignment to the terminal [S2].
<F115: Terminal S2 function > = "50"
Memo
• To always enable the functions, assign the functions to <F110: Always active function 1>,
<F127: Always active function 2>, and <F128: Always active function 3>.
Input terminal
Inverter
a-contact relay
CC
Input terminal
Inverter
Programmable controller
CC
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...