6. 30. 2 Setting overcurrent stall
<F601: Stall prevention level 1>
<F185: Stall prevention level 2>
■
Function
If the current exceeding the level set at Stall prevention level 1 or 2 is flowed, stall prevention
operation will be enabled to lower the output frequencies.
Setting the output frequency low lowers output current of fans and pumps, which prevents
overcurrent trip.
■
Parameter setting
■
How to set the parameter
100% reference is the inverter rated current.
To switch <F601: Stall prevention level 1> between <F185: Stall prevention level 2>, use signals to
input terminal. Assign "32: Stall prevention switching/Torque limit switching 1" to the unused input
terminal.
For details, refer to [7. 2. 1].
■
Display during the stall prevention operation
If the current exceeding the stall prevention level is about to flow, the output frequency will change.
At this time, the letter "C" will blink.
CAUTION
Prohibited
• Do not set the stall prevention level parameters (F601 and F185) extremely low.
Title
Parameter name
Adjustment range
Unit
Default setting
F601
Stall prevention level 1
10-200 (HD)
10-160 (ND)
%
*1
*1 Depending on capacity. For details, refer to [11. 6].
In case F601=199, 200(or 159, 160), stall prevention control is not activated.
F185
Stall prevention level 2
0.0Hz
STOP
13:53
F601 : Stall prevention level 1
Min: 10
Max: 200
X1000
X100
X10
X1
%
150
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...