E6582062
6. [Advanced] How to use parameters
6-48
4
4
6
9
6. 12. 1 Setting the preset-speed operation frequency
<F287: Preset speed 8>
<F288: Preset speed 9>
<F289: Preset speed 10>
<F290: Preset speed 11>
<F291: Preset speed 12>
<F292: Preset speed 13>
<F293: Preset speed 14>
<F294: Preset speed 15 / Forced run speed>
<F560: Preset speed operation style>
<F561: Operation function (1-speed)> through <F575: Operation function (15-speed)>
<F576: Operation function (0-speed)>
For details of preset speed operation, refer to [5. 3. 7].
6. 12. 2 Forced run in emergency
<F294: Preset speed 15 / Forced run speed>
■
Function
You can run the inverter at a specified speed (frequency) in emergencies or continue to forcibly run
it during slight failure. When the input terminal with the assigned function is turned ON, the inverter
runs at the frequency set with <F294: Preset speed 15 / Forced run speed> regardless of run and
frequency commands.
■
Parameter setting
■
Guideline for the setting
Assign the function to unused input terminal.
• When the inverter runs at a specified speed in an emergency
6. 12 Setting the preset-speed operation
frequency
Title
Parameter name
Adjustment range
Unit
Default setting
F294
Preset speed 15 / Forced
run speed
LL - UL
Hz
0.0
0.0Hz
STOP
13:13
F294 : Preset speed 15/Forced run
Min: 0.0
Max: 60.0
X1000
X100
X10
X1
Hz
0.0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...