6. 7. 1
Setting the starting frequency and the end
frequency
<F240: Start frequency>
<F243: End frequency>
■
Function
The frequency set for <F240: Start frequency> is instantly output at startup.
This parameter is used when the delayed response of starting torque caused by the acceleration/
deceleration time affects the frequency.
When the output frequency is decreased to the frequency set for <F243: End frequency>, the
frequency instantly becomes 0 Hz when stopping.
■
Parameter setting
■
Setting method
Use the parameters when the delayed response of starting torque caused by the acceleration/
deceleration time affects the frequency. For the setting values, 0.1-3.0 Hz (5 Hz or less) is
recommended. Overcurrent can be reduced by setting the value to the motor rated slippage or less.
Set the values so that <F240: Start frequency> is higher than <F243: End frequency>.
When <F240> is lower than <F243>, no operation is performed by any frequency command lower
than <F243>.
6. 7
Setting the start and end frequencies
Title
Parameter name
Adjustment range
Unit
Default setting
F240
Start frequency
0.0-10.0
Hz
0.1
F243
End frequency
0.0-30.0
Hz
0.0
0.0Hz
STOP
13:00
F240 : Start frequency
Min: 0.0
Max: 10.0
X1000
X100
X10
X1
Hz
0.1
Output frequency (Hz)
<F240: Start frequency>
<F243: End frequency>
Time (s)
0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...