E6582062
11. Table of parameters
11-34
1
9
11
F645
0645
Terminal RR PTC
trip
0: Disabled
1: Enabled
-
-
0
Y
F646
0646
PTC detection
resistance
100 - 9999
Ω
3000
Y
F647
0647
Control power
option failure
detection
0: Alarm (no detection
without option)
1: Alarm
2: Trip
-
-
0
Y
F648
0648
Number of starting
alarm
0.0 - 999.0
10000
times
999.0
Y
F649
0649
Fallback frequency
LL - UL
Hz
0.0
Y
F650
0650
Forced run
0: Disabled
1: Enabled
-
-
0
Y
F651
0651
Undertorque trip
0: Disabled
1: Enabled
-
-
0
Y
-
F652
0652
Undertorque
detection level
during power
running
0 - 250
%
0
Y
-
F653
0653
Undertorque
detection level
during regen
0 - 250
%
0
Y
-
F654
0654
Undertorque
detection time
0.00 - 10.00
s
0.50
Y
-
F655
0655
Undertorque
detection hysteresis
0 - 100
%
10
Y
-
F656
0656
PTC detection
temperature
0 - 200
°C
90
Y
F657
0657
Overload alarm
level
10 - 100
%
50
Y
F658
0658
Number of external
equipment starting
alarm
0.0 - 999.0
10000
times
999.0
Y
F659
0659
Cumulative
overcurrent level
10 - 200
%
100
Y
Title
Communication
No.
Parameter name
Adjustment range
Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......