6. [Advanced] How to use parameters
3
4
6
9
6. 7. 2
Run/stop with a frequency command
<F241: Run frequency>
<F242: Run frequency hysteresis>
■
Function
You can run/stop the motor with only a frequency command when a run command remains ON.
When the frequency command reaches the set frequency value, the inverter will start to run. When it
becomes below the set value, the inverter will stop.
■
Parameter setting
■
Setting method
When the frequency command reaches the setting value of <F241: Run frequency>, the inverter will
start to run. When the command becomes below the setting value, the inverter will stop.
To prevent the inverter from repeatedly running/stopping around the frequency set with <F241: Run
frequency>, use <F242: Run frequency hysteresis> to provide hysteresis.
Set the parameter, referring to the following figure.
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
Title
Parameter name
Adjustment range
Unit
Default setting
F241
Run frequency
0.0 - FH
Hz
0.0
F242
Run frequency hysteresis
0.0 - FH
Hz
0.0
0.0Hz
STOP
13:01
F241 : Run frequency
Min: 0.0
Max: 80.0
X1000
X100
X10
X1
Hz
0.0
Output frequency (Hz)
Frequency command
0
A
B
100%
<FH>
<F241>
<F242>
<F242>
<F241>
<F241>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...