5. [Fundamental operation] How to use parameters
3
4
5
9
5. 3. 6
Increasing starting torque
<vb: Manual torque boost 1>
■
Function
The starting torque is increased by increasing the setting value when starting torque is required. It is
valid when the setting value of <Pt: V/f Pattern> is "0: V/f constant", "1: Variable torque", or "7: V/f 5-
point setting".
■
Parameter setting
■
Reference of setting
100% is based on 200V, or 400V.
Set the value 2% of the default setting, generally.
Title
Parameter name
Adjustment range
Unit
Default setting
vb
Manual torque boost 1
0.00 - 30.00
%
*1
*1 Depending on the capacity. Refer to [11. 6].
Important
• The optimum value is programmed for each inverter capacity by default setting. When a value
larger than the reference value is set, an overcurrent trip may occur at startup.
• Repeated operation with excessive torque boost may cause failure of IGBT in the power circuit.
When larger stating torque is required, consider using vector control.
For details, refer to [5. 3. 4].
0.0Hz
STOP
15:25
Min: 0.00
Max: 30.00
X1000
X100
X10
X1
%
vb :Manual torque boost 1
4.80
Basic parameter
0
0
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...