E6582062
5. [Fundamental operation] How to use parameters
5-66
4
5
9
■
Switching with input terminal <F200> = "0"
Set <F200: Frequency command priority select> to "0".
Assign "104: FMOd/F207 priority switching" to an unused input terminal. For details, refer to [7. 2. 1].
• When the input terminal is OFF, run the motor with the frequency command set with <FMOd:
Frequency command select 1>.
• When the input terminal is ON, run the motor with the frequency command set with <F207:
Frequency command select 2>.
■
Automatic switching with switching frequency <F200> = "1"
Set <F200: Frequency command priority select> to "1" and set the frequency with <F208:
Frequency command switching frequency>.
• If the frequency command set with <FMOd: Frequency command select 1> is larger than the value
set with <F208>, the value set with <FMOd> becomes the frequency command.
• If the frequency command set with <FMOd> is larger than the value set with <F208>, the value set
with <F207: Frequency command value 2> becomes the frequency command.
Frequency set for <FMOd>
Frequency command
Frequency set for <F207>
OFF
ON
Command set for <FMOd>
given priority
Command set for <F207>
given priority
Ჸ
Frequency command signal
Time
ġ
<F208>
<F208>
<FMOd>
<FMOd>
<F208>
<F207>
<FMOd>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...