E6582062
6. [Advanced] How to use parameters
6-96
4
4
6
9
Set the torque limit values for the power running and regenerative torques at <F441: Power
running torque limit level 1> and <F443: Regenerative torque limit level 1>.
Set limit treatment of the constant output zone (weak magnetic field) at <F454: Torque limit in
field weakening>. You can select either constant output limit <F454> = "0" (default setting) or
constant torque limit <F454> ="1".
You can set four patterns each for the power running torque limit or the regenerative torque
limit at the parameter settings.
Patterns 1 to 4 can be switched by turning the input terminal ON/OFF.
Title
Parameter name
Adjustment range
Default setting
F440
Power running torque
limit input select 1
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11: -
12: F441
12
F442
Regenerative torque limit
input select 1
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11: -
12: F443
12
Title
Parameter name
Adjustment range
Unit
Default setting
F441
Power running torque
limit level 1
0.0-249.9
250.0: Disabled
%
250.0
F443
Regenerative torque limit
level 1
0.0-249.9
250.0: Disabled
%
250.0
F454
Torque limit in field
weakening
0: Constant power limit
1: Constant torque limit
0
Title
Parameter name
Adjustment range
Unit
Default setting
F444
Power running torque
limit level 2
0.0-249.9
250.0: Disabled
%
250.0
F445
Regenerative torque limit
level 2
%
250.0
F446
Power running torque
limit level 3
%
250.0
F447
Regenerative torque limit
level 3
%
250.0
F448
Power running torque
limit level 4
%
250.0
F449
Regenerative torque limit
level 4
%
250.0
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...