6. [Advanced] How to use parameters
3
4
6
9
Assign "32: Stall prevention switching/Torque limit switching 1" and "34: Torque limit switching
2" to the two unused input terminals.
2) When torque limits are applied by external signals
Torque limit value can be changed by external signals.
• When setting with input of 0 to 10 Vdc to terminal [RR]
Set "1" for <F440: Power running torque limit input select 1> and <F442: Regenerative
torque limit input select 1>.
• When setting with input of -10 to 10 Vdc to terminal [RX]
Set "2" for <F440: Power running torque limit input select 1> and <F442: Regenerative
torque limit input select 1>.
• When setting with input of 4 to 20 mAdc to terminal [II]
Set "3" for <F440: Power running torque limit input select 1> and <F442: Regenerative
torque limit input select 1>.
32: Stall prevention switching/
Torque limit switching 1
34: Torque limit switching 2
Torque limit level 1
OFF
OFF
Torque limit level 2
ON
OFF
Torque limit level 3
OFF
ON
Torque limit level 4
ON
ON
Memo
• Set the torque limit level to "250.0" when disabling this function.
• When <Pt: V/f Pattern>="0", "1", or "7", the torque limit will be disabled.
• When the current value is big, or the setting value of <F601: Stall prevention level 1> is small,
the stall preventive function may be active before torque limit and lower the frequency.
Forward run
Reverse run
Power
running
Regeneration
Positive torque
Negative torque
-250% torque
+250% torque
Power
running
Regeneration
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...