5. [Fundamental operation] How to use parameters
3
4
5
9
To increase the torque at low speeds, increase the setting value of <vb: Manual torque boost 1>. For
details, refer to [5. 3. 6].
1: Variable torque
This is applied to loads such as fans, pumps and blowers in which the torque is proportional to the
square of load motor speed.
2: Automatic torque boost
The load current in the speed range from startup to base frequency is detected and the output
voltage (torque boost) from the inverter is automatically adjusted. This gives steady torque for stable
operation.
It is applied to loads that require torque.
Operation may become unstable depending on loads. In this case, set <Pt> = "0: V/f constant" and
increase the value of <vb: Manual torque boost 1>.
Setting of motor parameters
When <Pt> is "2", setting of motor parameters is required.
Output frequency (Hz)
Output voltage (V)
0
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)
0
0
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)
0
: Automatically
adjusted to torque
boost value
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...