E6582062
5-5
5. [Fundamental operation] How to use parameters
3
4
5
9
21: RS485 communication (connector 1)
Remove the operation panel, connect a communication cable, and input a frequency command
through the RS485 communication.
For details, refer to [6. 38].
22: RS485 communication (connector 2)
Connect a communication cable to the RS485 communication connector 2 next to the control termi-
nal block, and input a frequency command through the RS485 communication.
For details, refer to [6. 38].
23: Communication option
Input a frequency command with a communication option command.
For details, refer to Each "Communication function instruction manual."
Memo
• The following functions set for the input terminal are always enabled regardless of the settings
of <CMOd: Run command select> and <FMOd: Frequency command select 1>.
- Reset (enabled at trip only)
- Standby
- External thermal trip
- Coast stop command
• Set <CMOd: Run command select> and <FMOd: Frequency command select 1> after stopping
the inverter.
You cannot set them during run.
However, when <F736: CMOd/FMOd change lockout during run> is set to "0: Unlocked", you
can change them during run. For details, refer to [6. 34. 1].
• The priority command from the communication or terminal precedes the setting of <FMOd:
Frequency command selection 1>.
• <F207: Frequency command select 2> is provided.
Use <FMOd: Frequency command select 1> in the default setting. However, you can switch
between two frequency command selections. For details, refer to [5. 4. 1].
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...