E6582062
5-57
5. [Fundamental operation] How to use parameters
3
4
5
9
The integral/derivative amount of PID control can be reset with an external signal. Assign function
number "52: PID differential/integral reset" to an input terminal.
<F366: PID1 differential gain>
This parameter adjusts the differential gain level of PID control. This gain increases the speed
of response to a rapid change in deviation (difference between the set value and the feedback
value). Note that setting the gain beyond necessity may cause fluctuations in output frequency,
and thus operation to become unstable.
The integral/derivative amount of PID control can be reset with an external signal. Assign "52:
PID differential/integral reset" to an input terminal.
4) Adjusting feedback input
Make adjustment by converting input level of the feedback value into frequency. Refer to [6. 6.
2].
PID set value
Residual deviation
Output frequency
Large
Small
Time
<F363>
<F363>
Feedback value
(Previous deviation) - (Current deviation)
Time
Small
Large
<F366>
<F366>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...